Fire Alarm (Detection) System types





A guide to Fire Alarm System types

Contents:
Conventional fire alarm systems
Two-wire fire alarm systems
Analogue addressable fire alarm systems
Wireless fire alarm systems
Aspirating smoke detection systems

1. Conventional fire alarm systems

Conventional, or four-wire, fire alarm systems have been extensively used in smaller properties such as shops and restaurants for many years.
Less expensive to purchase than other types of alarm system, they work by dividing the building into a number of detection zones, with the detectors and call points within each zone hardwired on dedicated circuits to the control panel. There may be multiple detectors on a single zone. A separate two-core, fire-protected cable for each alarm sounder or bell is needed because they are wired to different loops.
If a detector is activated, the control panel identifies the circuit that contains the triggered device and so indicates the zone from which the fire alarm has originated, but the area then has to be manually searched to pinpoint the individual device.

2. Two-wire fire alarm systems

Also designed for smaller operations, two-wire fire alarm systems are based on standard conventional system technology, but in a two-wire system, the detectors, call points and alarm devices for each zone are wired on the same set of two-core zone cables back to the control panel, enabling it to use a single circuit per zone both for detection and to power the sounders or sirens.
Although two-wire systems cost more to purchase than four-wire systems, they are quicker, more flexible and less expensive to install. Two-wire systems also provide more flexibility in operation, and have additional functionality, such as fault conditions, isolation, and detector recognition.

3. Analogue-addressable fire alarm systems

Analogue-addressable fire alarm systems give details on individual detectors, whereas conventional systems only give information about specific circuits or zones.
Addressable or “intelligent” fire alarm systems are designed for large commercial premises and more complex networked systems, since they are much more expensive and more complicated than conventional two- or four-wire systems, having increased flexibility, intelligence, speed of identification, and scope of control.
In addressable systems, different types of initiating devices are wired in one or more single loops around the premises, requiring less cabling than conventional systems, with each detector or call point having its own unique address.
The fire control panel receives information and status reports from each device and indicates its exact location if there is a fire, fault, smoke, heat, or contamination.

4. Wireless fire alarm systems

More expensive to buy, but more flexible, cheaper, and much quicker to install, wireless, or battery-powered radio-linked, fire alarm systems provide just as much protection as conventional wired systems and are useful when wired installations are not suitable (such as in grade-listed properties where wiring may be prohibited).
There are no cables between the detection devices and the control panel, so doing away with the need for long-term cable tests.
Wireless systems need to comply with EN54-25 standard. Increasingly sophisticated, today’s wireless fire alarm systems are much more reliable than the ones that originated in the 1980s and have multi-frequency links to eliminate signal blocking and collision, allowing a high margin of signal strength to be maintained.

5. Aspirating smoke detection systems


Although technically a detection solution, aspirating smoke detection systems are extremely sensitive and can detect very small or smoldering fires far quicker than other systems.
Aspirating systems use a fan to draw in air from around a building via a network of sampling pipes and sampling holes. The air is then passed through a highly sensitive precision detector that analyses it and generates warning signals of potential fire when it detects smoke particles.
Expensive to install and maintain, these systems are highly sensitive and can detect cool smoke that does not rise to the ceiling, as well as smoldering fires and particles given off by overloaded electrical cables. They are therefore especially useful where early warning is required.

মন্তব্যসমূহ

এই ব্লগটি থেকে জনপ্রিয় পোস্টগুলি

WHAT IS FIRE RATED GYPSUM DRYWALL?

Gypsum is approximately 21 percent by weight chemically combined water which greatly contributes to its effectiveness as a fire resistive barrier. When gypsum drywall is exposed to fire, the water is slowly released as steam, effectively retarding heat transmission. Fire rated gypsum drywall is more fire resistant because it contains glass fiber reinforcement and other additives within its specially formulated gypsum core to help it hold up longer to a fire exposure. Fire  rated drywall is referred to as “Type X” and must be third-party certified by an independent testing and listing agency such as UL (Underwriters Laboratories Inc.) and ULC (Underwriters’ Laboratories of Canada) to meet the fire performance requirements prescribed in the ASTM C1396 (CAN/CSA-A82.27) Standard Specification for Gypsum Board. Types of Fire Rated Gypsum: Type X fire rated gypsum drywall that is 5/8 -inch (15.9mm) thick and installed on each side of nominal 2-inch x 4-inch (38x89mm) wood

Pipe Schedule Method for Firefighting Sprinkler System

Pipe Schedule Method for Firefighting Sprinkler System                                     Pipe Schedule Method for Firefighting Sprinkler System  The water demand for firefighting sprinkler systems shall be determined by either the pipe schedule method or the hydraulic calculation method, in this article we will discuss the pipe schedule method. What is pipe schedule system?! According to NFPA 13, Pipe Schedule System is defined as sprinkler system in which the pipe sizing is selected from a schedule that is determined by the occupancy classification and in which a given number of sprinklers are allowed to be supplied from specific sizes of pipe. Where can we use pipe schedule method?! New systems of 465 m2 or less. Additions or modifications to existing pipe schedule systems. Classification of occupancies according to hazard NFPA 13 classifies the occupancies according to the quantity and combustibility of contents, the expected rates of heat rel

Method Statement for Installation of Fire Fighting Pipes and Fittings

1. SCOPE & PURPOSE 1.1 This “Method Statement” covers the nature and type of work for the Installation of Fire Fighting Pipes and fitting with Accessories and frequency at which the inspections are to be carried out. 1.2 This method statement gives guidelines contained herein so as to ensure that the job execution complies with the requirement of the specification and the authorities concerned and serves the intended purpose to satisfactory level. 1.3 This procedure is to be read in conjunction with the relevant ITP, outlining the responsibility and the quality verification to be performed by various parties. 2. REFERENCES & RELATED DOCUMENTS: 2.1 Project Quality Plan – PQP 2.2 Quality Control Plan – QCP 2.3 Specification Sec 2.4 Approved MAR 2.5 Approved Shop Drawings. 2.6 Manufacturer Product Data Sheets 2.7 Manufacturer Installation Recommendations 3 ABBREVIATIONS: 3.1 Ref. Quality Control Plan 4 RESPONSIBILITIES: 4.1 Ref. Quality Control